Schneider 140ARI03010 analog input module Modicon Quantum 8 I Ni / Pt 100, 200, 500, 1000
Description
Manufacture | Schneider |
Model | 140ARI03010 |
Ordering information | 140ARI03010 |
Catalog | Quantum 140 |
Description | Schneider 140ARI03010 analog input module Modicon Quantum 8 I Ni / Pt 100, 200, 500, 1000 |
Origin | Franch(FR) |
HS Code | 3595861133822 |
Dimension | 5cm*16.5cm*31cm |
Weight | 0.5kg |
Details
Range of product | Modicon Quantum automation platform |
---|---|
Product or component type | Analogue input module |
Analogue input number | 8 |
---|---|
Input type | Differential |
Addressing requirement | 9 input words |
Analogue input type | Temperature probe: - 100...450 °C for Pt 100, Pt 200, Pt 500, Pt 1000 Temperature probe: - 200...850 °C for Pt 100, Pt 200, Pt 500, Pt 1000 Temperature probe: - 60...180 °C for Ni 100, Ni 200, Ni 500, Ni 1000 Temperature probe: 0.5 mA for Ni 100, Ni 200, Ni 500, Ni 1000 Temperature probe: 2.5 mA for Pt 100, Pt 200, Ni 100, Ni 200 |
Analogue input resolution | 13 bits |
Input impedance | >= 10 MOhm |
Absolute accuracy error | 0.1 °C |
Linearity error | +/- 0.01 % full scale +/- 0.5 °C |
Accuracy drift according to temperature | +/- 0.5 °C at 25 °C +/- 0.9 °C at 0…60 °C |
Isolation between channels and bus | 1780 V AC 47...63 Hz for 60 s 2500 V DC for 60 s |
Isolation between channels | 300 Vrms AC |
Update time | 1200 ms 3 wires 640 ms 2 wires/4 wires |
Fault type | Broken wire Overtacking scale |
Marking | CE |
Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 8 LEDs (green) for channel is turned on 8 LEDs (red) for channel fault |
Bus current requirement | 200 mA |
Power dissipation in W | 1 W |
Module format | Standard |
Net weight | 0.3 kg |
Standards | UL 508 CSA C22.2 No 142 |
---|---|
Product certifications | FM Class 1 Division 2 cUL |
Resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 |
Resistance to electromagnetic fields | 10 V/m 80…1000 MHz conforming to IEC 801-3 |
Ambient air temperature for operation | 0…60 °C |
Ambient air temperature for storage | -40…85 °C |
Relative humidity | 95 % without condensation |
Operating altitude | <= 5000 m |