Emerson DeltaV KJ3001X1-BJ1 Discrete Out DO 24 VDC High Side
Description
Manufacture | Emerson |
Model | KJ3001X1-BJ1 |
Ordering information | KJ3001X1-BJ1 |
Catalog | Delta v |
Description | Emerson DeltaV KJ3001X1-BJ1 Discrete Out DO 24 VDC High Side |
Origin | Germany (DE) |
HS Code | 85389091 |
Dimension | 16cm*16cm*12cm |
Weight | 0.8kg |
Details
KJ3001X1-BJ1 DO, 8-Channel, 24 VDC, High Side Card Hazardous Atmosphere II 3 G Nemko No. 02ATEX431U EEx nA IIC T4 Power Specifications LocalBus power rating 12 VDC at 150 mA Field circuit rating 60 VDC at 1.5 A/channel, 6 A max. card Bussed field power rating 60 VDC (24 VDC nominal) 6 A card Environmental Specifications Ambient Temperature 0 to 60o C Shock 10g ½ Sinewave for 11 msec Vibration 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz Airborne Contaminants ISA-S71.04 –1985 Airborne Contaminants Class G3 Relative Humidity 5 to 95% Non-Condensing IP 20 Rating Terminal block key position B6 Note: Refer to the product label for serial number and location and date of manufacture. Refer also to the wiring diagram on the left side of the card. Warning: This product has specific instructions for installation, removal and operation in hazardous areas. Refer to document 12P2046 "DeltaV Scalable Process System Zone 2 Installation Instructions". Other installation instructions are available in the "Installing Your DeltaV Automation System" manual. Removal and Insertion Field power supplied to this device, either at the field terminal or as bussed field power through the carrier, must be removed before removing or connecting the device. This unit may be removed or inserted while system power is energized under the following conditions: (Note Only one unit at a time may be removed or inserted with system power energized.) • When used with KJ1501X1-BC1 System Dual DC/DC Power Supply operating on either 24 VDC or 12 VDC input power, The primary circuit wiring inductance less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance). • Non sparking field circuits MUST be deenergized before removing and inserting this product. A terminal block fuse may NOT be removed with field power energized for non-sparking circuits. A rotary keying system ensures compatibility between I/O cards and terminal blocks after installation is complete. The terminal block must have the keys set for the I/O card with which it is used. Maintenance and Adjustment This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.