Emerson A6500-CC System Communication Card
Description
Manufacture | Emerson |
Model | A6500-CC |
Ordering information | A6500-CC |
Catalog | CSI 6500 |
Description | Emerson A6500-CC System Communication Card |
Origin | Germany (DE) |
HS Code | 85389091 |
Dimension | 16cm*16cm*12cm |
Weight | 0.8kg |
Details
A6500-CC System Communication Card
The ModBus and Rack Interface Module is designed for high reliability for the plant’s most critical rotating machinery. It reads parameters from all AMS A6500 ATG modules and outputs these parameters through ModBus TCP/IP and/or ModBus RTU (serial). In addition, OPC UA is available for data transmission to third party systems. This 1-slot monitor is used together with other AMS A6500 ATG monitors to build a complete API 670 machinery protection monitor. Applications include steam, gas, compressors, and hydro turbo machinery. Operators are provided machinery health parameters in the control environment for seamless integration.
The module powers local graphical displays at the protection rack for machine and instrumentation readout. Either ModBus TCP/IP or ModBus RTU or OPC UA can be configured, or for redundant path, can be used simultaneously. Data Output RS 485 6 bus lines max. data rate according to EIA485 standard 512 kbit Ethernet Connector RJ45 Data rate 10/100 Mbit Max. cable length 100m Voltage 2V peak-to-peak Rated current 100 mA Rated power 200 mW USB Connection socket USB type B Data rate 12 Mbit/s Isolation Interface is connected to earth Modbus RS 485 According to EIA485 standard Data rate 9600 or 19.2 kBaud Voltage 200 mV peak-to-peak Rated current 1.6 mA Rated power 0.4 mW