Description
Manufacture | Invensys Triconex |
Model | TMR Analog Output Module |
Ordering information | 3805E |
Catalog | Tricon Sytems |
Description | Invensys Triconex 3805E Analog Output Module |
Origin | United States (US) |
HS Code | 85389091 |
Dimension | 16cm*16cm*12cm |
Weight | 0.8kg |
Details
Analog Output Modules
An analog output (AO) module receives output signals from the main processor module on each of three channels. Each set of data is then voted and a healthy channel is selected to drive the eight outputs. The module monitors its own current outputs (as input voltages) and maintains an internal voltage reference to provide self-calibration and module health information.
Each channel on the module has a current loopback circuit which verifies the accuracy and presence of analog signals independently of load presence or channel selection. The module’s design prevents a non-selected channel from driving an analog signal to the field. In addition, ongoing diagnostics are performed on each channel and circuit of the module. Failure of any diagnostic deactivates the faulty
channel and activates the Fault indicator, which in turn activates the chassis alarm. The module Fault indicator merely indicates a channel fault, not a module failure. The module continues to operate properly with as many as two channels failed. Open loop detection is provided by a LOAD indicator which activates if the module is unable to drive current to one or more outputs.
The module provides for redundant loop power sources with individual power and fuse indicators called PWR1 and PWR2. External loop power supplies for analog outputs must be provided by the user. Each analog output module requires up to 1 amp @ 24-42.5 volts. A LOAD indicator activates
if an open loop is detected on one or more output points. PWR1 and PWR2 are on if loop power is present. The 3806E High Current (AO) module is optimized for turbomachinery applications. Analog output modules support hotspare capability which allows online replacement of a faulty module.
The analog output module requires a separate external termination panel (ETP) with a cable interface to the Tricon backplane. Each module is mechanically keyed to prevent improper installation in a configured chassis.
Datasheet link
Product detail pictures:
Related Product Guide:
Our enhancement depends around the sophisticated devices ,exceptional talents and repeatedly strengthened technology forces for Best Invensys Triconex Company – Invensys Triconex 3805E Analog Output Module – RuiMingSheng , The product will supply to all over the world, such as: Haiti, Barbados, Durban, Customer satisfaction is our first goal. Our mission is to pursue the superlative quality, making continual progress. We sincerely welcome you to make progress hand in hand with us, and construct a prosperous future together.
By Lindsay from Johor - 2018.06.28 19:27
The customer service staff's answer is very meticulous, the most important is that the product quality is very good, and packaged carefully, shipped quickly!
By Quyen Staten from Burundi - 2017.09.26 12:12