Description
Manufacture | Woodward |
Model | 5466-355 |
Ordering information | 5466-355 |
Catalog | MicroNet Digital Control |
Description | Woodward 5466-355 NETCON REMOTE CHASSIS TRANSCEIVER MODULE |
Origin | United States (US) |
HS Code | 85389091 |
Dimension | 16cm*16cm*12cm |
Weight | 0.8kg |
Details
Module Description
This Actuator Driver module receives digital information from the CPU and generates four proportional actuator-driver signals. These signals are proportional and their maximum range is 0 to 25 mAdc or 0 to 200 mAdc. Figure 10-5 is a block diagram of the four-channel Actuator Driver module. The system writes output values to dual-port memory through the VME-bus interface.
The microcontroller scales the values using calibration constants stored in EEPROM, and schedules outputs to occur at the proper time. The microcontroller monitors the output voltage and current of each channel and alerts the system of any channel and load faults. The system can individually
disable the current drivers. If a fault is detected which prevents the module from operating, by either the microcontroller or the system, the FAULT LED will illuminate.
10.3.3—Installation
The modules slide into card guides in the control’s chassis and plug into the motherboard. The modules are held in place by two screws, one at the top and one at the bottom of the front panel. Also at the top and bottom of the module are two handles which, when toggled (pushed outward), move the modules out just far enough for the boards to disengage the motherboard connectors.
10.3.4—FTM Reference
See Chapter 13 for complete field wiring information for the Four Channel Actuator Module FTM. See Appendix A for part number cross reference for modules, FTMs, and cables.
10.3.5—Troubleshooting
Each I/O module has a red fault LED, which indicates the status of the module. This LED will help with troubleshooting if the module should have a problem. A solid red LED indicates that the actuator controller is not communicating with the CPU module. Flashing red LEDs indicate an internal problem with the module, and module replacement is recommended.
Datasheet link
Product detail pictures:
Related Product Guide:
Assume full accountability to satisfy all demands of our consumers; reach ongoing advancements by endorsing the expansion of our purchasers; come to be the final permanent cooperative partner of clients and maximize the interests of clientele for Best 9907-028 Supplier - Woodward 5466-355 NETCON REMOTE CHASSIS TRANSCEIVER MODULE – RuiMingSheng , The product will supply to all over the world, such as: Georgia, Hungary, Latvia, All the imported machines effectively control and guarantee the machining precision for the products. Besides, we have a group of high-quality management personnels and professionals, who make the high-quality products and have the ability to develop new products to expand our market home and abroad. We sincerely expect customers come for a blooming business for both of us.
By Stephen from Singapore - 2018.06.05 13:10
Cooperate with you every time is very successful, very happy. Hope that we can have more cooperation!
By Teresa from Morocco - 2018.02.04 14:13