9907-147 Company - Woodward 5466-355 NETCON REMOTE CHASSIS TRANSCEIVER MODULE – RuiMingSheng
9907-147 Company - Woodward 5466-355 NETCON REMOTE CHASSIS TRANSCEIVER MODULE – RuiMingSheng Detail:
Description
Manufacture | Woodward |
Model | 5466-355 |
Ordering information | 5466-355 |
Catalog | MicroNet Digital Control |
Description | Woodward 5466-355 NETCON REMOTE CHASSIS TRANSCEIVER MODULE |
Origin | United States (US) |
HS Code | 85389091 |
Dimension | 16cm*16cm*12cm |
Weight | 0.8kg |
Details
Module Description
This Actuator Driver module receives digital information from the CPU and generates four proportional actuator-driver signals. These signals are proportional and their maximum range is 0 to 25 mAdc or 0 to 200 mAdc. Figure 10-5 is a block diagram of the four-channel Actuator Driver module. The system writes output values to dual-port memory through the VME-bus interface.
The microcontroller scales the values using calibration constants stored in EEPROM, and schedules outputs to occur at the proper time. The microcontroller monitors the output voltage and current of each channel and alerts the system of any channel and load faults. The system can individually
disable the current drivers. If a fault is detected which prevents the module from operating, by either the microcontroller or the system, the FAULT LED will illuminate.
10.3.3—Installation
The modules slide into card guides in the control’s chassis and plug into the motherboard. The modules are held in place by two screws, one at the top and one at the bottom of the front panel. Also at the top and bottom of the module are two handles which, when toggled (pushed outward), move the modules out just far enough for the boards to disengage the motherboard connectors.
10.3.4—FTM Reference
See Chapter 13 for complete field wiring information for the Four Channel Actuator Module FTM. See Appendix A for part number cross reference for modules, FTMs, and cables.
10.3.5—Troubleshooting
Each I/O module has a red fault LED, which indicates the status of the module. This LED will help with troubleshooting if the module should have a problem. A solid red LED indicates that the actuator controller is not communicating with the CPU module. Flashing red LEDs indicate an internal problem with the module, and module replacement is recommended.
Datasheet link
Product detail pictures:
Related Product Guide:
We depend on sturdy technical force and continually create sophisticated technologies to meet the demand of 9907-147 Company - Woodward 5466-355 NETCON REMOTE CHASSIS TRANSCEIVER MODULE – RuiMingSheng , The product will supply to all over the world, such as: Lahore, azerbaijan, Cambodia, We expect to provide products and services to more users in global aftermarket markets; we launched our global branding strategy by providing our excellent products all over the world by virtue of our well reputed partners letting global users keep pace with technology innovation and achievements with us.