Description
Manufacture | Bently Nevada |
Model | 3500/60-01-00 |
Ordering information | 163179-01 |
Catalog | 3500 |
Description | Bently Nevada 3500/60-01-00 163179-01 Temperature Modules |
Origin | United States (US) |
HS Code | 85389091 |
Dimension | 16cm*16cm*12cm |
Weight | 0.8kg |
Details
Description
The 3500/60 & 61 modules provide six channels of temperature monitoring and accept both Resistance Temperature Detector (RTD) and Thermocouple (TC) temperature inputs. The modules condition these inputs and compare them against user-programmable alarm setpoints. The 3500/60 and 3500/61 provide identical functionality except that the 3500/61 provides recorder outputs for each of its six channels while the 3500/60 does not.
The user programs the modules to perform either RTD or TC temperature measurements using the 3500 Rack Configuration Software. Different I/O modules are available in RTD/TC non-isolated or TC isolated versions. The user can configure the RTD/TC non-isolated version to accept either TC or RTD, or a mixture of TC and RTD inputs. The TC isolated version provides 250 Vdc of channel-to-channel isolation to protect against external interference.
When used in a Triple Modular Redundant (TMR) configuration, temperature monitors must be installed adjacent to each other in groups of three. When used in this configuration, the system employs two types of voting to ensure accurate operation and to avoid single-point failures.
Ordering Information
For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from Bently.com.
Without Recorder Outputs
3500/60-AA-BB
A:I/O Module Type
0 1 RTD/TC Non-isolated I/O Module Internal Terminations
0 2 RTD/TC Non-isolated I/O Module External Terminations
0 3 TC Isolated I/O Module Internal Terminations
0 4 TC Isolated I/O Module External Terminations
0 5 RTD/TC Non-isolated I/O Module with Internal Barriers
B:Agency Approval Option
0 0 None
0 1 CSA/NRTL/C (Class 1, Div 2)
0 2 ATEX/ IECEx/ CSA (Class 1, Zone 2)
3500/60 -Specific
163179-01 3500/60 Temperature Monitor (without recorders)
133827-01 3500/60 RTD/TC Non-Isolated I/O Module, External Terminations.
133819-01 3500/60 RTD/TC non-Isolated I/O Module, Internal Terminations
133835-01 3500/60 TC Isolated I/O Module, Internal Terminations.
133843-01 3500/60 TC Isolated I/O Module, External Terminations.
136711-01 3500/60 RTD/TC I/O Module with Internal Barriers and Internal Terminations. (Not-Isolated)
Datasheet link
Product detail pictures:
Related Product Guide:
Our mission is usually to turn into an innovative provider of high-tech digital and communication devices by furnishing benefit added design and style, world-class manufacturing, and service capabilities for 330103-00-06-10-02-00 Company - Bently Nevada 3500/60-01-00 163179-01 Temperature Modules – RuiMingSheng , The product will supply to all over the world, such as: Russia, Albania, Mauritius, Thus far, our item associated with printer dtg a4 may be shown in most foreign nations as well as urban centers, which are sought after simply by targeted traffic. We all highly imagine that now we have now the full capacity to present you with contented merchandise. Desire to collect requests of your stuff and produce the long-term co-operation partnership. We very seriously promise:Csame top quality, better price; exact same selling price, higher quality.